ProSoft Technology MVI46-MCM User Manual

Page 20

Advertising
background image

Configuring the MVI46-MCM Module

MVI46-MCM ♦ SLC Platform

User Manual

Modbus Communication Module

Page 20 of 108

ProSoft Technology, Inc.

March 29, 2011

File M0

Offset

Register

Content

Description

N10:27

28

5027

Output Offset

This parameter specifies the offset address in the
internal Modbus database for network requests for
Modbus function 1, 5, or 15 commands. For
example, if the value is set to 100, an address
request of 0 will return the value at register 100 in
the database.

N10:28 29

5028

Holding

Register

Offset

This parameter specifies the offset address in the
internal Modbus database for network requests for
Modbus 3, 6, or 16 commands. For example, if the
value is set to 50, an address request of 0 will
return the value at register 50 in the database.

N10:29

30

5029

Command Count

This parameter specifies the number of commands
to be processed for the port. Enter a value of 0 to
100.

N10:30 31

5030

Minimum

Command

Delay

This parameter specifies the number of
milliseconds to wait between the initial issuance of
a command. This parameter can be used to delay
all commands sent to slaves to avoid "flooding"
commands on the network. This parameter does
not affect retries of a command as they will be
issued when failure is recognized. Enter a value in
the range of 0 to 65535.

N10:31 32

5031

Command

Error

Pointer

This parameter sets the address in the internal
Modbus database where the command error data
will be placed. If the value is set to -1, the data will
not be transferred to the database. Enter a value of
0 to 4999.

N10:32

33

5032

Response Timeout

This parameter represents the message response
timeout period in 1 ms increments. This is the time
that a port configured as a master will wait before
re-transmitting a command if no response is
received from the addressed slave. The value is set
depending on to communication network used and
the expected response time of the slowest device
on the network.

N10:33

34

5033

Retry Count

This parameter specifies the number of times a
command will be retried if it fails. Enter a value in
the range of 0 to 10.

N10:34

35

5034

Error Delay Count

This parameter specifies the number of polls to be
skipped on the slave before trying to re-establish
communications. After the slave fails to respond,
the master will skip commands to be sent to the
slave the number of times entered in the
parameter. Enter a value in the range of 0 to
65535.

N10:35 36

5035

Reserved

N10:36

37

5036

Use Guard Band
Timer

Use packet gap timeout for messages (Yes or No).
Use only in multi-drop applications.

N10:37

38

5037

Guard Band Timeout

A value of 0 uses the default baud rate or you can
set a value in milliseconds (0 to 65535)

N10:38 39

5038

Spare

N10:39 40

5039

Spare

Advertising