Configuring the MVI46-MCM Module

MVI46-MCM ♦ SLC Platform

User Manual

Modbus Communication Module

Page 24 of 108

ProSoft Technology, Inc.

March 29, 2011

To enable the Guard Band Timeout parameter:

1 First of all, enable the functionality through the Use Guard Band Timer

parameter as follows:

Use Guard Band Timer = Y

2 Then, set the Guard Band Timeout as follows:

Guard Band Timeout = 0

This configuration will set the module to use a pre-defined time interval for
Modbus message recognition calculated for each baud rate. This should
provide optimal performance for most applications.

The following guard band timer values will be automatically used by the module
with the default parameter value (Guard Band Timeout = 0) is selected:

Baud

Guard Band Timer (ms)

110 350

150 256

300 128

600 64

1200 32

2400 16

4800 8

9600 4

19200 2

28800 2

38400 2

57600 1

115200 1

If you still observe a considerable number of communication errors, try to
increase the Guard Band Timeout value (in milliseconds) until the network
performance is improved.