Diagnostics and Troubleshooting

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 35 of 108

March 29, 2011

During module configuration, the OK LED is red and the APP and BP ACT LEDs
will be on. If the LEDs are latched in this mode for a long period of time, look at
the configuration error words in the configuration request block. The structure of
the block is shown in the following table.

M0 Offset

Description

Length

0 9000

1

1 Spare

1

2

Port 1 Configuration Errors

1

3

Port 2 Configuration Errors

1

The port configuration error words have the following definitions:

Bit

Description

Value

0

Type code is not valid. Enter a value from 0 (master)to 1 (slave).

0x0001

1

Protocol parameter is not valid.

0x0002

2

Termination type parameter is not valid.

0x0004

3

Baud rate parameter is not valid.

0x0008

4

Parity parameter is not valid.

0x0010

5

Data bits parameter is not valid.

0x0020

6

Stop bits parameter is not valid.

0x0040

7

Command count parameter is not valid.

0x0080

8

Retry count parameter is not valid.

0x0100

9

Spare

0x0200

10

Spare

0x0400

11

Spare

0x0800

12

Spare

0x1000

13

Spare

0x2000

14

Spare

0x4000

15

Spare

0x8000

Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.

If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.