5.4

MVI46-MCM Database Definition

This section contains a listing of the internal database of the MVI46-MCM
module. This information can be used to interface other devices to the data
contained in the module.

Register Range

Modbus Low

Modbus High

Content

Size

0 to 4999

40001

45000

User Data

5000

5000 to 5009

45001

45010

Backplane Configuration

10

5010 to 5039

45011

45040

Port 1 Setup

30

5040 to 5069

45041

45070

Port 2 Setup

30

5200 to 6199

45071

46070

Port 1 Commands

1000

6200 to 7199

46071

47070

Port 2 Commands

1000

7200 to 7232

47201

47233

Misc. Status Data

33

7600 to 7799

47601

48000

Command Control

200

The User Data area holds data collected from other nodes on the network
(master read commands) or data received from the processor (write blocks).
Additionally, this data area is used as a data source for the processor (read
blocks) or other nodes on the network (write commands).