Diagnostics and Troubleshooting

MVI46-MCM ♦ SLC Platform

User Manual

Modbus Communication Module

Page 34 of 108

ProSoft Technology, Inc.

March 29, 2011

4.1

LED Status Indicators

The LEDs indicate the module’s operating status as follows:

LED Color

Status

Indication

P1 Green

On Data is being transferred between the module and a

remote terminal using the Configuration/Debug port.

Off

No data is being transferred on the Configuration/Debug
port.

P2

Green

On

Data is being transferred between the module and the
Modbus network on its Modbus Port 1.

Off

No data is being transferred on the port.

P3 Green

On Data is being transferred between the module and the

Modbus network on its Modbus Port 2.

Off

No data is being transferred on the port.

APP

Amber

On

The MVI46-MCM is working normally.

Off

The MVI46-MCM module program has recognized a
communication error on one of its Modbus ports.

BP ACT

Amber

On

The LED is on when the module is performing a write
operation on the backplane.

Off

The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the
LED should blink rapidly on and off.

OK Red/

Green

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

Red

The program has detected an error or is being configured.
If the LED remains red for over 10 seconds, the program
has probably halted. Remove the card from the rack and
re-insert the card to restart the module’s program.

BAT

Red

Off

The battery voltage is OK and functioning.

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for
24 hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.