ProSoft Technology MVI46-MCM User Manual

Page 4

Advertising
background image

Battery Life Advisory

The MVI46, MVI56, MVI56E, MVI69, and MVI71 modules use a rechargeable Lithium Vanadium Pentoxide battery to
backup the real-time clock and CMOS. The battery should last for the life of the module. The module must be
powered for approximately twenty hours before the battery becomes fully charged. After it is fully charged, the battery
provides backup power for the CMOS setup and the real-time clock for approximately 21 days. When the battery is
fully discharged, the module will revert to the default BIOS and clock settings.

Note: The battery is not user replaceable.

Markings

Electrical Ratings

Backplane Current Load: 800 mA @ 5 Vdc

Operating Temperature: 0°C to 60°C (32°F to 140°F)

Storage Temperature: -40°C to 85°C (-40°F to 185°F)

Shock: 30g Operational; 50g non-operational; Vibration: 5 g from 10 Hz to 150 Hz

Relative Humidity 5% to 95% (without condensation)

All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground conductors must be at least
4mm(squared).

Label Markings

Agency Approvals and Certifications

Agency Applicable

Standards

ANSI / ISA

ISA 12.12.01 Class I Division 2, GPs A, B, C, D

CSA/cUL

C22.2 No. 213-1987

CSA CB Certified

IEC61010

ATEX

EN60079-0 Category 3, Zone 2
EN60079-15

243333


Advertising