ProSoft Technology MVI46-MCM User Manual

Page 84

Advertising
background image

Reference MVI46-MCM

♦ SLC Platform

User Manual

Modbus Communication Module

Page 84 of 108

ProSoft Technology, Inc.

March 29, 2011

5.6.2 Read Coil Status (Function Code 01)

Query
This function allows the user to obtain the ON/OFF status of logic coils used to
control discrete outputs from the addressed Slave only. Broadcast mode is not
supported with this function code. In addition to the Slave address and function
fields, the message requires that the information field contain the initial coil
address to be read (Starting Address) and the number of locations that will be
interrogated to obtain status data.

The addressing allows up to 2000 coils to be obtained at each request; however,
the specific Slave device may have restrictions that lower the maximum quantity.
The coils are numbered from zero; (coil number 1 = zero, coil number 2 = one,
coil number 3 = two, and so on).

The following table is a sample read output status request to read coils 0020 to
0056 from Slave device number 11.

Adr

Func

Data Start Pt Hi Data Start Pt Lo Data # Of Pts Ho Data # Of Pts Lo

Error Check Field

11

01

00 13 00 25 CRC

Response
An example response to Read Coil Status is as shown in Figure C2. The data is
packed one bit for each coil. The response includes the Slave address, function
code, quantity of data characters, the data characters, and error checking. Data
will be packed with one bit for each coil (1 = ON, 0 = OFF). The low order bit of
the first character contains the addressed coil, and the remainder follow. For coil
quantities that are not even multiples of eight, the last characters will be filled in
with zeros at high order end. The quantity of data characters is always specified
as quantity of RTU characters, that is, the number is the same whether RTU or
ASCII is used.

Because the Slave interface device is serviced at the end of a controller's scan,
data will reflect coil status at the end of the scan. Some Slaves will limit the
quantity of coils provided each scan; thus, for large coil quantities, multiple PC
transactions must be made using coil status from sequential scans.

Adr Func Byte

Count

Data Coil
Status 20 to

27

Data Coil
Status 28 to

35

Data Coil
Status 36 to

43

Data Coil
Status 44 to

51

Data Coil
Status 52 to

56

Error
Check

Field

11

01

05

CD 6B B2 OE 1B CRC

The status of coils 20 to 27 is shown as CD(HEX) = 1100 1101 (Binary). Reading
left to right, this shows that coils 27, 26, 23, 22, and 20 are all on. The other coil
data bytes are decoded similarly. Due to the quantity of coil statuses requested,
the last data field, which is shown 1B (HEX) = 0001 1011 (Binary), contains the
status of only 5 coils (52 to 56) instead of 8 coils. The 3 left most bits are
provided as zeros to fill the 8-bit format.

Advertising