ProSoft Technology MVI46-MCM User Manual

Page 68

Advertising
background image

Reference MVI46-MCM

♦ SLC Platform

User Manual

Modbus Communication Module

Page 68 of 108

ProSoft Technology, Inc.

March 29, 2011

Block Request from Processor to Module

M1 Offset

Description

Length

7800

3000 or 3100

1

7801

Number of Slaves in Block

1

7802 to 7927

Slave Indexes

126

The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block.

Block Response from Module to Processor

M0 Offset

Description

Length

0

3000 or 3100

1

1

Number of Slaves Processed

1

Ladder logic can be written to override the value in the slave status table to
enable the slave (state value of 1) by sending a special block. Port 1 slaves are
enabled using block 3001, and Port 2 slaves are enabled using block 3101. Each
block contains the slave node addresses to enable.

Block Request from Processor to Module

M1 Offset

Description

Length

7800

3001 or 3101

1

7801

Number of Slaves in Block

1

7802 to 7927

Slave Indexes

126

The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block.

Block Response from Module to Processor

M0 Offset

Description

Length

0

3001 or 3101

1

1

Number of Slaves Processed

1

Advertising