10. INSTALLATION

10-21

Output signal (contact closure signal)

J10 (Arrival alarm)

J11

J12

Pin no.

Designation

Pin no.

Designation

Pin no.

Designation

#1

Alarm out 1 (H)

#1

Alarm out 2 (H)

#1

Alarm out 3 (H)

#2

Alarm out 1 (C)

#2

Alarm out 2 (C)

#2

Alarm out 3 (C)


Selection of output data format

The output data format is selectable by changing a jumper block; A for RS-422

and B for NMEA. For example, to select NMEA for J4, change the jumper block

from A to B on J401 and J402. Do the same on J5 thru J9.

No. Jumper Pin

no. Jumper No. Jumper

J4

J401/J402 (A)

J5

J501/J502 (A)

J6

J601/J602 (A)

J7

J701/J702 (A)

J8

J801/J802 (A)

J9

J901/J902 (B)

Default jumper setting is shown in parenthesis.


Self test 2

The test requires an external loop to check I/O. Follow the steps below to carry

out the test.

1) Set the #4 segment of DIP switch S1 to the ON position.

2) Temporarily disconnect input and output connectors J2 and J4.

3) Solder a jumper block between J2 and J4; #3 and #4 of J2 are connected to

#1 and #2 of J4, respectively.
Jumper block consists of XH-6 pin and 4 pin connectors with two short wires

as below.

XH, 6 pin XH, 4 pin

#3 - - - #1

#4 - - - #2

4) Change the jumper block between J2 and J5; J2/J6, J2/J7, J2/J8, J2/J9,

J3/J4, J3/J5, J3/J6, J2/J7, J2/J8, J2/J9.