Document: LT0273

MXP Loop Filter Board

Page 9-10

24 March 2006

Issue 1.5

9.7

MIM800 / CIM800 / MIM801 PROCESSING

The MIM800 and CIM800 return a value which depends on the external resistance across
the contact terminals and which can be modelled by the equation –

VALUE = 226 * (150 + 3) / (150 + Rext + 3)


The MIM801 returns a value which depends on the external resistance across the contact
terminals and which can be modelled by the equation –

VALUE = 226 * (Rext + 3) / (150 + Rext + 3)
(unless Rext is open circuit, then value = 255)

(Note 150 represents an internal 150

Ω resistor, 3 represents a 3Ω FET on resistance, and

226 represents (3.3V - DIODEV) / 3.3V * 255

Graphs of these values are show in Figure 9.7. Also shown are the default thresholds, and
the interpretations of the input ranges between the thresholds.

0

20

40

60

80

100

120

140

160

180

200

220

240

0

50

100

150

200

250

300

350

400

450

500

550

600

R

Read

ing

MIM801

MIM800

N/O : Optional S/C Fault

N/O : Alarm

N/C:
O/C Fault

N/C : S/C Fault

N/O :
Alarm

N/O :
Optional S/C Fault

Normal

Normal

N/O :
O/C Fault

N/C :
Alarm

N/O :
O/C
Fault
N/C :
Alarm

176

122

110

40

50

170

Figure 9.7 MIM800 / MIM801 Reading versus resistance


The usual parameters are as follows –

MIM800 / CIM800

MIM801

P0 P1 P2 P3 P4 P5

No alarm resistor
(Default)

122 50 0 110 170 0

With alarm
resistor

176