MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-34

24 March 2006

Issue 1.5

For the MIM801 the default value of 15 selects normally closed operation with interrupt on
alarm (e.g. for New Zealand callpoints). Setting the mode to 13 disables interrupt on alarm
(e.g. for heat circuits or other non-immediate alarm conditions). Setting the mode to 12
enables normally open operation and then changing parameter 5 to 40 enables short circuit
fault detection.

Normally Open

Parameter Description

Default

4 No

interrupt

Mode

6 Interrupt

4

P0

Normal to alarm threshold

122

P1

Normal to o/c threshold

50

Alarm to s/c threshold
0

No alarm resistor

P2

176

100 ohm alarm resistor

0

P3

P4

P5

P6

Normally Closed

Parameter Description

Default

Mode

Change to 5 to select normally closed operation

4

P0

Normal to s/c threshold

122

P1

Normal to alarm threshold

50

P2

P3

P4

P5

P6

3.16.5 MX4428

PROGRAMMING OPTIONS - MIM801

Normally Open

Parameter Description

Default

Mode

Change to 12 to select normally open operation

15

P0

P1

P2

P3

Normal to alarm threshold

110

P4

Normal to o/c threshold

170

Alarm to s/c threshold
0

No alarm resistor

P5

40

100 ohm alarm resistor

0

P5

P6

Normally Closed

Parameter Description

Default

Value Description
13 No

interrupt

Mode

15

Interrupt, does not use AVF even if enabled

15

P0

P1

P2

P3

Normal to s/c threshold

110

P4

Normal to alarm threshold

170

P5

P6