1 programming, 2 output state under exceptional circumstances – Tyco MX4428 User Manual

Page 27

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-11

3.3.1 PROGRAMMING

The programming of the output functions is done by setting the “mode” value for the RIM800,
SNM800, and 814I, and by one of the 7 device parameters for the 814H, 814PH, and
814CH. The LPS800 is programmed as an SNM800.

For example the following are the settings for the 814I.

Mode

Functional Base Control

Remote LED Control

0

Circuit Alarm

Circuit Alarm

1 Circuit

Alarm

Relay

2

Circuit Alarm

Point Alarm

4 Relay

Circuit

Alarm

5 Relay

Relay

6 Relay

Point

Alarm

8

Point Alarm

Circuit Alarm

9 Point

Alarm

Relay

10

Point Alarm

Point Alarm


The value must be chosen from the above table to give the desired settings for controlling
the functional base and the remote LED.

For the 814PH and 814CH, programming of the “enhancement multiplier” is included in the
same parameter. The desired enhancement multiplier must be multiplied by 16 and the
result added to the above numbers. The tables in the sections for these detectors (3.9.3 and
3.10.3) include the result when the default enhancement multiplier is used.

For the 814H detector and for an 814PH or 814CH with enhancement disabled, the
“enhancement multiplier” is irrelevant and therefore the above numbers may be entered
directly if desired. The global defaults for parameter 6 for all these detector types should
always include the desired enhancement multiplier * 16.

For the SNM800, other options are also included in the mode. Refer to section 3.22.4 for
details.

3.3.2 OUTPUT

STATE

UNDER

EXCEPTIONAL CIRCUMSTANCES

All outputs retain their state if the MX4428 stops polling the responder (e.g. processing is
stopped), or if the MXP stops polling the devices (e.g. due to a new configuration download
from the MX4428). If a detector is removed from a relay or sounder base, the relay or
sounder output turns off.

If power to the MXP is lost, loop powered sounder bases turn off. RIM800 and SNM800
outputs, relay bases and possibly externally powered sounder bases usually retain their
state until MXP power is restored, then turn off when polling resumes (which may take some
minutes if the MXP has been off for some hours and lost its configuration), then revert to ON
after a few seconds if this is the correct state.

Advertising