MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-38

24 March 2006

Issue 1.5

3.18

CP820 MANUAL CALL POINT

3.18.1 GENERAL

The CP820 Manual Call Point consists of a MIM800 mounted on a Break Glass Switch
assembly. The MIM800 is factory programmed with a different type-id to allow the CP820 to
be distinguished from a generic MIM800.

The normal response time to an input change of state is 0 – 5 seconds, as each device is
polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation
can be enabled. Interrupt operation allows a change to be signalled by the device so that the
MXP detects the change immediately, rather than waiting for the next poll of the device.

The CP820 is made without an EOL resistor and no wiring fault monitoring is provided as all
the wiring is internal.

The CP820 device processing will not use AVF, even if it is enabled for the circuit the CP820
is allocated to.

3.18.2 MX4428

PROGRAMMING OPTIONS - CP820

The mode determines whether interrupt operation is enabled or not. A value of 0 (default)
means interrupt is disabled, while a value of 2 enables interrupt operation.

Parameter Description

Default

0 No

interrupt

Mode

2 Interrupt

0

P0

Normal to alarm threshold

122

P1

P2

P3

P4

P5

P6