MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-24

24 March 2006

Issue 1.5

The remaining parameters should not need changing.

Parameter Description

Default

Value Enhance

CO

sensitivity with heat
Rate of Rise

Heat Type
A – rate of rise enabled
B – rate of rise disabled

0 Yes

A

1 Yes

B

2 No

A

3 No

B

6

Yes

No heat alarm

Mode

7

No

No heat alarm

2

P0

CO Pre Alarm Threshold

80

CO Alarm Threshold
Value Threshold
60 23ppm
93 38ppm

(default)

P1

160 66ppm

(alternate)

93

P2

Heat fixed temperature pre-alarm threshold

°C 56

(

°C)

Heat fixed temperature alarm threshold

°C

Value Usage
57 New

Zealand

P3

63

Australian Types A / B

63 (

°C)

b3:b0

ROR Pre alarm Threshold

7 (12

°C/min)

P4

b7:b4

ROR Alarm Threshold

Number + 5 gives the
Threshold in

°C/min

9 (14

°C/min)

b3:b0

CO Filter Divisor

3

P5

b7:b4

CO Step Limit

3

Enhancement multiplier (default 12) * 16 plus value below
Value Functional

Base

Control

Remote LED
Control

Result with
default enh
multiplier

0

Circuit Alarm

Circuit Alarm

192

1 Circuit

Alarm

Relay

193

2

Circuit Alarm

Point Alarm

194

4 Relay

Circuit

Alarm

196

5 Relay

Relay

197

6 Relay

Point

Alarm

198

8

Point Alarm

Circuit Alarm

200

9 Point

Alarm Relay

201

P6

10

Point Alarm

Point Alarm

202

192