22 snm800 sounder notification module, 1 general, 2 snm800 specifications – Tyco MX4428 User Manual

Page 61

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-45

3.22

SNM800 SOUNDER NOTIFICATION MODULE

3.22.1 GENERAL

The SNM800 Sounder Notification Module is suitable for relay outputs which require
supervision of the load wiring and optional supervision of the DC power supply (if any).

When inactive, a reverse polarity supervision voltage is applied to the load wiring. The load
devices must therefore have internal or external reverse blocking diodes.

The load supervision can detect short and open circuit states on the load wiring only when
the relay is inactive.

The 24V DC supply may be supervised.

The load must be isolated from ground and all voltage sources. All inductive loads (e.g. bells
or relays) must have back-emf diodes or other noise clamping devices fitted.

Recognition of a fault condition takes about 30 seconds.

3.22.2 SNM800

SPECIFICATIONS

Dimensions

Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 450uA (typical)

LED On : 3.0mA (typical)

Output Circuit EOL

27k ohms, 0.5 watt

Contact Rating

2A 30Vdc


Load must be isolated from ground and all supplies.