Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-33

Maximum input cable length

10m

EOL

200

Ω + / - 5%.

Alarm

Resistance

100

Ω + / - 5%. (if used)

3.16.3 FIELD

WIRING

TB1

TB1

TB2

TB

2

L+

L+

L+

L+

L-

L-

L-

L-

NEXT
DEVICE

NEXT
DEVICE

PREVIOUS

DEVICE

PREVIOUS

DEVICE

200
ohm
EOL

200
ohm
EOL

100
ohm

ANALOG LOOP

ANALOG LOOP

MIM800
Mini Module

MIM800
Mini Module

Sh

Sh

IN- IN+ O- O+

IN- IN+ O- O+

LED

LED

TB1

TB2

L+

L+

L-

L-

NEXT
DEVICE

PREVIOUS

DEVICE

200
ohm
EOL

ANALOG LOOP

MIM801
Mini Module

Sh

IN- IN+ O- O+

LED

Normally Open

(default for MIM800, option for MIM801.)

N/O with S/C fault

(for MIM800 or MIM801)

Normally Closed

(default for MIM801,option for MIM800)

Requires Param_2 = 176 (MIM800),
Param_5 = 40 (MIM801)

Inputs must be voltage free.

Figure 3.4 CLEAN CONTACT DEVICE CONNECTION TO MIM800 / MIM801

3.16.4 MX4428

PROGRAMMING

OPTIONS - MIM800 / MIM801

The mode sets the operating configuration.

For the MIM800 the default value of 4 selects normally open operation with no interrupt. A
mode of 6 selects normally open with interrupt on alarm. Changing parameter 2 to 176
enables short circuit fault detection. Setting the mode to 5 enables normally closed
operation.