Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device

Processing

Issue 1.5

24 March 2006

Page 9-11

These are designed for the following configurations–

Device

Mode

Contact R

EOL R

Max Wiring R

N/O Not

used 200

Ω 50Ω

N/O

100

Ω 200Ω 10Ω

MIM800
CIM800

N/C 200

Ω 50Ω

N/O Not

used 200

Ω 50Ω

N/O

100

Ω 200Ω 10Ω


MIM801

N/C 200

Ω 50Ω


Parameters for alternative contact and EOL resistors could be derived from the graphs in
Figure 9.7.

9.7.1

ALGORITHM - MIM800, CIM800

The unverified input condition is evaluated according to the following table, depending on the
mode (N/O or N/C) and the values of parameters P0, P1, and P2.

P2=0

P2 not = 0

N/O

N/C

P2<=reading<=255

Short

circuit

fault

P0<=reading<=255 P0<=reading<P2

Alarm


Short

P1<=reading<P0 P1<=reading<P0 Normal

Normal

0<=Reading < P1

0<=Reading < P1

Open circuit fault

Alarm


Changes in these states are verified as described in section 9.22.

For the CIM800, if either input is in fault, the point will be in fault. If either input is in alarm,
the point will be in alarm. It may therefore be in fault and alarm at the same time.

9.7.2

ALGORITHM - MIM801

The unverified input condition is evaluated according to the following table, depending on the
mode (N/O or N/C) and the values of parameters P0, P1, and P2

P5=0

P5 not = 0

N/O

N/C

P4<=reading<=255 P4<=reading<=255 Open

circuit

fault

Alarm

P3<=reading<P4 P3<=reading<P4 Normal

Normal

0<=Reading < P3

P5<=Reading < P3

Alarm

0<=Reading < P5

Short circuit fault

Short circuit fault


Changes in these states are verified as described in section 9.22.

Advertising