17 cim800 contact input module, 1 general, 2 cim800 specifications – Tyco MX4428 User Manual

Page 51

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-35

3.17

CIM800 CONTACT INPUT MODULE

3.17.1 GENERAL

The CIM800 Contact Input Module is suitable for interfacing voltage free contacts, e.g.
switches, relay contacts, flow switches, or non-indicating detectors. It has two inputs, the
state of which are ORed together to generate the point status. Therefore unused inputs must
be terminated with the EOL resistor.

The CIM800 may be used in normally open or normally closed configurations, and the
normally open configuration may or may not include short circuit fault monitoring. Refer to
Figure 3.5 for wiring topology.

The normal response time to an input change of state is 0 – 5 seconds, as each device is
polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation
can be enabled. Interrupt operation allows a change to be signalled by the device so that the
MXP detects the change immediately, rather than waiting for the next poll of the device.

The CIM800 can only interrupt on “closing” contacts, and interrupt operation is only
applicable for normally open contacts. Transitions from closed to open will always require up
to 5 seconds to be recognised. Therefore it cannot be used for callpoints on NZ systems.

Fault supervision is provided by default with a 200

Ω EOL resistor - open circuit fault in a

normally open configuration and short circuit fault in a normally closed configuration. In
addition the normally open configuration can be programmed to also generate fault on short
circuit. In this case only one alarm contact is allowed, a 100

Ω resistor must be wired in

series with the alarm contacts, and the fault threshold must be specially programmed - set
Parameter 2 to 176.

Recognition of a fault condition takes about 30 seconds.

WARNING

DO NOT JOIN INPUT WIRING BETWEEN INPUTS OR MODULES OR TO ANYTHING
OTHER THAN VOLTAGE FREE CONTACTS

3.17.2 CIM800

SPECIFICATIONS

Dimensions

Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 275uA (typical)

LED on : 2.8mA (typical)

Contact Inputs

Monitoring Voltage

5V

Line

Resistance

10

Ω max

EOL

200

Ω + / - 5%.

Alarm

Resistance

100

Ω + / - 5% (if used).