2 dim800 specifications – Tyco MX4428 User Manual

Page 57

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-41

DIM800 DETECTOR
INPUT MONITOR

L+

L+

L-

L-

NEXT
DEVICE

PREVIOUS

DEVICE

ANALOG LOOP

ANALOG LOOP

A+ A- B+ B-

+

24V

CO

M

EXT
PSU

+

-

4k7 EOL

4k7 EOL

Conventional
Detectors
(refer appropriate
wiring diagrams)

Refer text for
voltage
requirements

Unused inputs (A or B) must be
terminated with 4k7 EOL.

Figure 3.6 DIM800 Field Wiring

3.20.2 DIM800

SPECIFICATIONS

Dimensions

Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

L-, L+

Loop Supply Voltage

20V – 40V

Loop Supply Current

Standby/Alarm Loop Current : 100uA (typical)

EOL

4k7 + / - 1%.

Detector Load

3.0mA max per circuit

External Current (normal)

7.5mA (excluding detectors)

External Current (shorted)

30 - 50mA (depends on supply voltage)

External Supply Voltage

Refer to Table 3-4 for each detector.

Maximum Line Resistance

50

Ω (with detectors)

1750

Ω (with hard contacts only)

Short Circuit Fault Option

Maximum line resistance 34

Ω

Minimum Detector Alarm Voltage 5.0V