MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-50

24 March 2006

Issue 1.5

3.24.3

MX4428 PROGRAMMING OPTIONS - VLC800

The only programmable items for the VLC800 are

1. The pre alarm threshold.
2. The source of the remote LED output.
3. The source of the onboard relay output and external relay output (they operate

together).


The VLC800 shares default values with the 814H, 814PH, and 814PHFL. However the alarm
threshold is fixed at 100 regardless of any default setting. The default pre alarm setting of 68
translates to 68% of the alarm value which although a suitable value, can be changed if
required.

Parameter Description

Default

P0

Pre Alarm Threshold

68

192 plus value below
Value

Relay Control

Remote LED
Control

Resulting
parameter

0

Circuit Alarm

Circuit Alarm

192

1

Circuit Alarm

Relay Logic

193

2

Circuit Alarm

Point Alarm

194

4

Relay Logic

Circuit Alarm

196

5

Relay Logic

Relay Logic

197

6

Relay Logic

Point Alarm

198

8

Point Alarm

Circuit Alarm

200

9

Point Alarm

Relay Logic

201

P6

10

Point Alarm

Point Alarm

202

192


AVF may be applied to the circuit the VLC800 point maps to.