3 field wiring, 4 mx4428 programming options - cim800 – Tyco MX4428 User Manual

Page 52

Advertising
background image

MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-36

24 March 2006

Issue 1.5

3.17.3 FIELD

WIRING

CIM800 CONTACT MODULE

CIM800 CONTACT MODULE

CIM800 CONTACT MODULE

TB1

TB1

TB1

TB2

TB2

TB2

L+

L+

L+

A+

A+

A+

L+

L+

L+

B+

B+

B+

L-

L-

L-

A-

A-

A-

L-

L-

L-

B-

B-

B-

NEXT
DEVICE

NEXT
DEVICE

NEXT
DEVICE

PREVIOUS

DEVICE

PREVIOUS

DEVICE

PREVIOUS

DEVICE

200
ohm
EOL

200
ohm
EOL

100
ohm

100
ohm

200
ohm
EOL

200
ohm
EOL

200
ohm
EOL

200
ohm
EOL

ANALOG LOOP

ANALOG LOOP

ANALOG LOOP

Normally Open

Normally Open, S/C = Fault

Normally Closed

Requires Param_2 = 176

Unused inputs (A or B) must be terminated with
a 200 ohm EOL resistor.

A and B inputs must be voltage free.


Figure 3.5 CLEAN CONTACT DEVICE CONNECTION TO CIM800

3.17.4

MX4428 PROGRAMMING OPTIONS - CIM800

The mode sets the operating configuration. The default value of 8 selects normally open
with no interrupts, whereas a value of 10 enables interrupt on alarms.

A mode of 9 selects normally closed operation. Interrupt is not available.