2 fault and alarm event log – Tyco MX4428 User Manual

Page 83

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Event Log and Status at MX4428

Issue 1.5

24 March 2006

Page 6-3

6.2

FAULT AND ALARM EVENT LOG

The table below lists examples of event log items which are produced at the MX4428 panel.
Circuit / point event logging must be enabled to see the events listed below. Zone events are
not shown.

Event on MXP

Event Logged

Event Logged on return to
normal

Database tx from F4000
to MXP

RSP 1 DATABASE TX
START

RSP 1 DATABASE TX
COMPLETE

Point Alarm

CCT 1/1 ALARM
PNT 1/30 ALARM

CCT 1/1 ALARM CLR
PNT 1/30 ALARM CLR

Point Fault

CCT 1/1 FAULT
PNT 1/20 FAULT

PNT 1/20 FAULT CLR
CCT 1/1 NORMAL

Point Pre-Alarm

PNT 1/3 PRE-ALARM

PNT 1/3 ALARM CLR

SNM800 wiring o/c or
s/c

RLY 1/1 FAULT
PNT 1/26 SUPERVISION
FAULT

PNT 1/26 NORMAL OFF
RLY 1/1 NORMAL

SNM800 Supply Fail

RLY 1/1 FAULT
PNT 1/26 LOAD SUPPLY
FAIL

PNT 1/26 NORMAL OFF
RLY 1/1 NORMAL

SNM800 / RIM800
checkback fail

RLY 1/1 FAULT
PNT 1/24 CONTROL CB
FAIL

PNT 1/24 CONTROL CB NML
(RIM800)
PNT 1/26 NORMAL ON (or OFF)
(SNM800)
RLY 1/1 NORMAL

DIM800 Supply Low

CCT 1/1 FAULT
PNT 1/25 FAULT
PNT 1/25 LOAD SUPPLY
FAIL

PNT 1/25 FAULT CLR
CCT 1/1 NORMAL

Point scan fail

PNT 1/22 NODE FAIL
CCT 1/1 FAULT

PNT 1/22 NODE FAIL CLR
CCT 1/1 NORMAL

Detector calibration fault

CCT 1/1 FAULT
PNT 1/2 FAULT
PNT 1/2 PARAMETER
ERROR

CCT 1/1 NORMAL
PNT 1/2 FAULT

Loop o/c

RSP 1 LOOP OPEN
CIRCUIT

RSP 1 LOOP OPEN CIRCUIT
CLEARED

Loop line A or B short or
overload

RSP 1 LOOP SHORT
CIRCUIT

RSP 1 LOOP SHORT CIRCUIT
CLEARED

Type Mismatch

PNT 1/1 POINT TYPE
MISMATCH

PNT 1/1 POINT TYPE OK

Foreign Device

PNT 1/3 FOREIGN DEVICE

(note- re-logged after DP command)

System Test or autotest
- device not normal at
start

PNT 1/2 TEST START NOT NML
CCT 1/1 FAIL SELF TEST 3 1

System Test or autotest
- device alarm test fail

PNT 1/1 ALARM TEST FAIL
CCT 1/1 FAIL SELF TEST 3 1

Zone alarm test device
fail

PNT 1/1 ALARM TEST FAIL

Diagnostic Pollscan result -Correct point found

P1/22 LINE 1 OK LINE 2 OK LED OFF
TYPE

OK

Diagnostics Pollscan result - point not found

P1/100 LINE 1 FAULT LINE 2 FAULT LED

OFF TYPE OK

Diagnostic Pollscan result -Type mismatch

P1/20 LINE 1 OK LINE 2 OK LED OFF
TYPE

BAD


Note “Type Mismatch” means a different device type was found at an address, from the type
programmed in the panel configuration for that address. An example of this would be a
MIM800 found at an address that is configured to have an 814PH. Refer to section 3.1.1 for
details of some device substitutions that are accepted without generating a fault.