4 isolator base loading, 5 example – Tyco MX4428 User Manual

Page 25

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-9

3.2.4 ISOLATOR

BASE

LOADING

If isolator bases are being used, calculate the sum of the “IB Units” from Table 3-2 for each
section of cable between isolator bases (or between the last isolator base and the end of a
cable spur). Include only one of the detectors at the ends of the section. The sum for any
section must not exceed 100.

See also section 4.1.3 for details of AS1670 requirements and section 4.1.4 for details of
NZS4512 requirements.

3.2.5 EXAMPLE

Consider an MXP monitoring 200 * 814PH detectors with 10 814SB Sounder Bases set to
High, on a 1300 metre long loop, using 1.5mm

2

wire. The cable is divided (with 9 Isolator

Bases) into 10 segments with 1 Sounder Base and 20 detectors on each segment.

(i)

Calculate DC Load


IA = 195 x 275uA

(No. of detectors in NORMAL)

+ 5 x 3.0mA

(No. of detectors with Alarm LEDs turned on, assume limited to
5 max by MXP)

+ 10 x 15mA

(Number of 814SB Sounder Bases)

+ 9 x 80uA

(Number of Isolator Bases)

(Ref Table 3-2. Note 1mA = 1000uA)

= 220mA which is well under 400mA

For the voltage drop calculation, assume the worst case in the first instance, i.e. that
all devices are at the far end of 1300 metres. The loop resistance of 1.5mm

2

wire is

25

Ω per 1000m and the isolator base resistance is 0.25Ω.

Total R

= 25

Ω x 1.3 + 9 x 0.25Ω

=

34.75

Ω.

Voltage drop = 34.75 x 0.220 = 7.7V, which is well under the maximum allowable of
16V.


(ii)

Calculate AC Load


AC Units

=

200 x 1 (detectors)

+ 10 x 2.4 (Sounder Bases)

+ 10 x 0.1 (Isolator Bases)

=

225 which is less than the maximum allowable of 250.


Cable length is well under the limits specified in Table 3-3.


(iii)

Calculate IB Load


IB Units for each section

= 20 * 1.2 (814PH) + 1 * 2.5 (814SB)

= 26.5 which is less than 100.


As all parameters are within the specified limits, the design is satisfactory.