24 vlc-800mx vesda lasercompact, 1 general, 2 vlc800 specifications – Tyco MX4428 User Manual

Page 65

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-49

3.24

VLC-800MX VESDA LASERCOMPACT

3.24.1 GENERAL

The VLC800 is a derivative of the standard VESDA LaserCOMPACT product family, with the
primary difference that it communicates directly on the MX loop.

VESDA LaserCOMPACT detectors provide very early warning of potential fire conditions by
drawing air samples through 25mm pipe up to 80m long. Smoke is sampled through holes in
the pipe and transported to the detector by an integrated aspirator or fan. Holes are
positioned according to the application and often follow the spacing of standard conventional
point detectors. Where necessary, sampling points can be constructed using capillary
extensions.

The VLC800 alarm sensitivity can be set to between 0.005% obscuration / m and 20%
obscuration / m. A PC plugged into the VLC800 is required to set the sensitivity, to normalise
the airflow, and perform other setup functions. The sensitivity is NOT controlled at the
MX4428.

Refer to Tyco Safety Products UK publication 17A-03-VLC for further details on installing,
commissioning and servicing the VLC-800.

3.24.2 VLC800

SPECIFICATIONS

Environment:

Indoor Application only

IP Rating:

IP30

Operating Temperature:

Detector Ambient:

-10°C to +39°C

Sampled Air:

-20°C to +60°C

Relative Humidity:

10-95% non-condensing

Dimensions:
Height:

225mm

Width:

225mm

Depth:

85mm

Weight: 1.9kg
Sampling Network:

Maximum Area Coverage: 800m

2

Maximum Pipe length:

80m with up to 15* holes,

or 2 x 50m with up to 9* holes per pipe

Pipe Size:

ID15 - 21mm

OD

25mm

‘*’ more holes may be used on networks designed using the VESDA Aspire
pipe modelling software.


External 24V dc:

Supply Voltage:

18 to 30V dc

Current Consumption:

Standby: 225mA

Alarm:

245mA

MX Loop:
Normal:

300uA

Non operational (VLC off): 300uA

Alarm:

300uA

Alarm with external relay:

dependant on the relay

Alarm with external LED:

3.3mA

Onboard relay: rated 2A @ 30V dc