9.8.4

SUPPLY MONITORING - DIM800

The DIM800 supply is monitored with input AI3 of the device ASIC. If the supply voltage is
less than 18V, a SUPPLY FAIL fault is generated. (The threshold can be changed with
parameter 3 if needed.) If the supply fails completely, a DIM800 with revision less than 10
will stop responding to polls and a NODE FAIL fault is generated.

9.9

RIM

PROCESSING

9.9.1 POSITION

MONITORING

Correct Relay state

DI0

Condition

0 OK

Not activated

1 Relay

Stuck

0 Relay

Stuck

Activated

1 OK


Changes in these states are verified as described in section 9.22. Verified faults
representing a “relay stuck” condition are logged as CONTROL CB FAIL at the MX4428,
with the return to normal event logged as CONTROL CB NML.

9.10

SNM

PROCESSING

9.10.1 PROGRAMMING

Supply Monitoring Required

DO6

No 1

Yes 0


9.10.2 SUPPLY

FAULT

DETERMINATION

Input AI1

Condition

AI1 > P3

Supply Fault

AI1 <= P3

Supply OK


Note that Parameter 3 cannot reliably be adjusted to monitor supplies of different voltages.

9.10.3

EOL AND POSITION MONITORING

Correct Relay Position

AI0

Condition

P1 < AI0 <= 255

Open circuit fault

P2 <= AI0 <= P1

Normal

0 <= AI0 < P2

Short circuit fault

Not activated

Any No

Position

Fault

Any

No Open Circuit Fault

No Short Circuit Fault

P1 <= AI0 < 255

No Relay Stuck Fault

Activated

0 <= AI0 < P1

Relay Stuck Fault


Changes in these states are verified as described in section 9.22.