MX4428 MXP Engineering / Technical Manual

Document: LT0273

Responder Loop Design Considerations

Page 2-4

24 March 2006

Issue 1.5

Number of Logical

Responders

(NLR)

Number of Circuits (Relays)

available

(NC = 4 * NLR)

Number of Points per circuit

(relay)

PC = 200/NC

Total Quantity of Points

in Last Circuit

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

4
8

12
16
20
24
28
32
36
40
44
48
52
56
60
64
68
72
76
80
84
88
92
96

100
104
108
112
116
120
124
128
132
136
140
144
148
152
156
160
164
168
172
176
180
184
188
192
196
200

50
25
16
12
10

8
7
6
5
5
4
4
3
3
3
3
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

50
25
24
20
10
16
11
14
25

5

28
12
47
35
23
11
66
58
50
42
34
26
18
10

2

97
93
89
85
81
77
73
69
65
61
57
53
49
45
41
37
33
29
25
21
17
13

9
5
1

Table 2-1 Point Allocation For Various Numbers of Logical Responders