MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-6

24 March 2006

Issue 1.5

All loop devices are rated at a loop voltage of 20Vdc - 40Vdc and a signalling voltage of 2V
p-p – 6V p-p. Alarm Currents specified do not include remote indicators. Add 7mA for each
remote indicator.

DEVICE FUNCTION

Comments

814I

Ionisation Smoke Detector

Requires base

814H

Heat Detector

Requires base

814PH

Photo Smoke + Heat
Detector

Requires base

814P

Photo Smoke Detector

Requires base

814CH

CO + Heat Detector

Requires base

MIM800

Mini Input Module

EOL 200

Ω

Alarm R (if used) 100

Ω

Max Wiring R 10

Ω

MIM801

Mini Input Module
(normally closed interrupt)

N/O mode - as MIM800
N/C -
EOL 200

Ω

Max wiring R 50

Ω

CIM800

Contact Input Module

EOL 200

Ω

Alarm R (if used) 100

Ω

Max Wiring R 10

Ω

DIM800

(Conventional) Detector
Interface Monitor

EOL 4k7
Requires separate supply.

CP820

Call Point

FP0838, FP0839

NZ Call Point

RIM800

Relay Interface Module

2A 30Vdc

SNM800

Sounder Notification
Module (Supervised relay
output)

2A 30Vdc.
Requires external supply.

LPS800

Loop Powered Sounder
Module

Provides 24V at up to 75mA

MUB

Standard Base

5BI

Isolator Base

814SB

Loop Powered Sounder
Base

Selectable tone (not AS2220 or ISO8201)
Adjustable sound level

802SB

Loop Powered Sounder
Base

Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Adjustable sound level

812SB

Loop Powered Sounder
Base

Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)

901SB

Externally Powered
Sounder Base

Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Adjustable Sound Level.
Requires external 24V

MkII

Sounder

Bases

912SB

Externally Powered
Sounder Base

Selectable tone (Including AS2220 and ISO
8201 Evacuation tone)
Requires external 24V

814RB

Relay Base

1A 30Vdc
2 pole changeover

VLC800

Vesda aspirating smoke
detector

Requires external supply. Requires PC to
set up.

Table 3-1 Compatible Device Summary

The MXP will allow some alternative devices to be used without generating a fault, where the
inserted device can provide all the features of the configured device. This includes an 814PH
or 814CH used where an 814H was programmed, a CIM800 used where a MIM800 was
programmed, and an 814PH used where an 814P was programmed.