2 standard related, 3 specifications – Tyco MX4428 User Manual

Page 9

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Introduction

Issue 1.5

24 March 2006

Page 1-3

Volume 9,

F4000 MPR Technical & Engineering Manuals, Volume 9-1 provides

technical details on the MPR and Addressable devices, and Volume 9-2 provides
Engineering Design information for correctly engineering the MPR loop (LT0139/LT0140).

Volume 10, MX4428 AS4428.1 LCD Operator’s Manual, provides a guide to the
operation and maintenance of MX4428 AS4428.1 LCD FIP panels with Version 3.10
software, according to Australian Standard AS4428.1, and New Zealand Standard NZS4512.
This manual (LT0249) is provided as standard with MX4428 panels.

Volume 11, MX4428 MXP Technical / Engineering Manual, (LT0273) provides technical
details on the MXP and its addressable devices, and provides engineering design
information for correctly engineering the MXP loop.

F4000 Point Text Installation & Operation Manual (LT0228) provides details of the Point
Text expansion option.

SmartConfig User Manual (LT0332) provides details on programming an MX4428
database using the SmartConfig program.

1.2.2 STANDARD

RELATED

This manual makes reference to the following Australian Standards –

AS1603.4

Automatic Fire Detection and Alarm Systems
Part 4 - Control and Indicating Equipment


AS1670.1

Automatic Fire Detection and Alarm Systems-
System Design, Installation, and Commissioning.


AS1851.8

Maintenance of Fire Protection Equipment
Part 8 - Automatic Fire Detection and Alarm Systems.


AS4428.1

Automatic Fire Detection and Alarm Systems. Control and Indication
Equipment.

This manual makes reference to the following New Zealand Standard –

NZS4512

Automatic Fire Alarm Systems in Buildings.

1.3

SPECIFICATIONS

Inputs / Outputs

1. Standard F4000 / MX4428 Responder Loop.

2. Analogue Loop for up to 200 MX devices, with a

maximum output current = 400mA.

3. RS232 Diagnostics Port.

Card Size

194mm * 140mm * 35mm.

Supply Voltage

17.0VDC to 30.0VDC.

Current Consumption

50mA to 1.3A depending on the number and type of
devices connected. Refer to section 5.1.

Operating Temperature Range -5

°C to +50°C, 10% to 93% RH non condensing.