MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-46

24 March 2006

Issue 1.5

3.22.3 SNM800

FIELD

WIRING

SNM800 SOUNDER
NOTIFICATION MODULE

L+

L+

L-

L-

NEXT
DEVICE

PREVIOUS

DEVICE

ANALOG LOOP

ANALOG LOOP

S+ S- R+ R- I+ I-

I+ I-

Power
Supply

+
-

Power to
next
device

27k
0.5W
EOL

+

+

+

-

-

-

Figure 3.8 SNM800 Field Wiring


It is recommended that the external supply covers only one zone, or the power wiring be
arranged so that an open circuit in the power feed cannot affect more than one zone. A loop
arrangement with supervision and a reverse-feed relay can be used to achieve this - refer to
Product Bulletin PBF0200.

3.22.4

MX4428 PROGRAMMING OPTIONS - SNM800

The mode selects the control source for the SNM800 output, load supervision, and EOL
supervision. By default (mode = 15) the output follows the logical relay, the external supply is
supervised, and the EOL is supervised.

Parameter Description

Default

Mode Output

Control Monitor

Supply ?

Monitor
EOL ?

8 Cct

Alarm No No

9 Cct

Alarm No Yes

10 Cct

Alarm Yes No

11 Cct

Alarm Yes Yes

12 Relay

No No

13 Relay

No Yes

14 Relay

Yes No

Mode

15 Relay

Yes Yes

15

P0

P1

Normal to o/c fault threshold

221

P2

Normal to s/c fault threshold

20

P3

Supply fault threshold

200

P4

P5

P6