21 rim800 relay interface module, 1 general, 2 rim800 specifications – Tyco MX4428 User Manual

Page 59: 3 rim800 field wiring

Advertising
background image

Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-43

3.21

RIM800 RELAY INTERFACE MODULE

3.21.1 GENERAL

The RIM800 Relay Interface Module is suitable for relay outputs which require clean voltage
free contacts and no supervision. For example it can be used to signal states to other
systems (e.g. BMS or security systems), or to energise loads that do not need to be
supervised, e.g. Door Holders.

3.21.2 RIM800

SPECIFICATIONS

Dimensions:

Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

L-, L+

Supply Voltage

20V – 40V

Supply Current

Standby Current : 285uA (typical)

LED on : 2.8mA (typical)

Contact Rating

2A 30Vdc

0.6A 120Vac (not permitted by AS / NZS standards)

0.3A 240Vac (not permitted by AS / NZS standards)

3.21.3 RIM800

FIELD

WIRING

The field wiring is shown in Figure 3.7.

RIM800 RELAY MODULE

TB1

TB2

L+

L+

L-

L-

NEXT
DEVICE

PREVIOUS

DEVICE

ANALOG LOOP

O+ O-

N/O COM N/C

PSU

Normally
Energised
Load

Normally
DeEnergised
Load

Make no connection to O+ and O- terminals

Figure 3.7 RIM800 Field Wiring

Advertising