Galaxy GHDX2-2430S/R-24F4D Installation and Hardware Reference Manual

System

Monitoring

3-8

FLASHING indicates the batteries are being charged.

Table 3-6: BBU LED Definitions



IMPORTANT!

In addition to BBU failure itself and the charger failure, the subsystem may

also light the BBU fault LED when the following occur:

1. The temperature sensor embedded with the charger circuit reports a

temperature reading exceeding 45 degree Celsius.

2. The BBU (battery backup unit) has been charged for over 12 hours. The

BBU charger will enter a timer fault state.

When the above conditions occur, the charger circuit will enter a low-power

and self-protection state.

You may correct the faults when receiving a “

BBU Thermal

Shutdown/Enter Sleep-Mode!” event message:

1.

Check proper ventilation within the subsystem. You may also check the

readings from other sensors within the enclosure. Airflow might have been

disrupted by the absence of one or several major modules or the failure of

a cooling fan. Once the thermal condition is improved, charging will

resume automatically.

2.

If a new battery module has been charged for over twelve (12) hours and

this event is issued, you may remove and re-install the battery module. An

empty battery module may take more than 12 hours to be fully charged.

There is a timer embedded with the charger, doing so can reset the timer.

Charging will resume automatically.

3.

Whenever you install/re-install a BBU, the subsystem recognizes a BBU

only after a system reset.