Galaxy GHDX2-2430S/R-24F4D Installation and Hardware Reference Manual

System

Monitoring

3-10

LED

Status

OFF

The respective cooling fan is operating normally.

ON

The respective cooling fan has failed and the module must be

replaced.

Table 3-8: Cooling Fan Module LED Definitions



3.3. Audible

Alarm

Different controller environmental and operational parameters (such as temperature, etc.)

have been assigned a range of values between which they can fluctuate. If either the

upper or lower thresholds are exceeded, an audible alarm will automatically be triggered.

The alarm will also be triggered when an active component of the subsystem fails. If the

subsystem manager is onsite and is alerted by the alarm, the manager needs to read the

error message on the LCD screen or on the PC terminal to determine what has triggered

the alarm and then take appropriate actions to rectify the problem.

WARNING!

Whenever an alarm is triggered, you must determine the cause of the problem. If

the audible alarm is ignored or not taken seriously and the problem is not rectified,

permanent damage to the system can result.

3.3.1

Default Threshold Values

Table 3-9 shows the default threshold values for the subsystem. If these values are

surpassed, the alarm will sound. The enclosure sensor default is set at a higher value than

the suggested ambient temperature threshold; however, it is crucial you maintain an

ambient temperature below 40ºC (and below 35ºC if BBUs are applied) at your

installation site.

Parameter

Upper Threshold

Lower Threshold

+3.3V +3.6V

+2.9V

+5V +5.5V

+4.5V

+12V +13.2V

+10.8V

Enclosure Ambient

40ºC

0ºC