5 general specifications, Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 104

Advertising
background image

5 General Specifications

Mains supply (L1, L2, L3):

Supply voltage

380-500 V ±10%

Supply voltage

525-690 V ±10%

Supply frequency

50/60 Hz

Max. imbalance temporary between mains phases

3.0 % of rated supply voltage

True Power Factor (λ)

≥ 0.9 nominal at rated load

Displacement Power Factor (cos

ϕ) near unity

(> 0.98)

Switching on input supply L1, L2, L3 (power-ups)

maximum 1 time/ 2 min.

Environment according to EN60664-1

over-voltage category III/pollution degree 2

The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 500/600/690 V maximum.

Motor output (U, V, W):

Output voltage

0 - 100% of supply voltage

Output frequency

0 - 800* Hz

Switching on output

Unlimited

Ramp times

0.01 - 3600 sec.

* Voltage and power dependent

Torque characteristics:

Starting torque (Constant torque)

maximum 160% for 60 sec.

*

Starting torque

maximum 180% up to 0.5 sec.

*

Overload torque (Constant torque)

maximum 160% for 60 sec.

*

Starting torque (Variable torque)

maximum 110% for 60 sec.

*

Overload torque (Variable torque)

maximum 110% for 60 sec.

*Percentage relates to the nominal torque.

Digital inputs:

Programmable digital inputs

4 (6)

Terminal number

18, 19, 27

1)

, 29, 32, 33,

Logic

PNP or NPN

Voltage level

0 - 24 V DC

Voltage level, logic'0' PNP

< 5 V DC

Voltage level, logic'1' PNP

> 10 V DC

Voltage level, logic '0' NPN

2)

> 19 V DC

Voltage level, logic '1' NPN

2)

< 14 V DC

Maximum voltage on input

28 V DC

Pulse frequency range

0 - 110 kHz

(Duty cycle) Min. pulse width

4.5 ms

Input resistance, R

i

approx. 4 kΩ

AF-650 GP High Power Operating Instructions