Af-650 gp high power operating instructions, 2 initial commissioning – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 73

Advertising
background image

4.1.2 Initial Commissioning

The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using Keypad (read table from
left to right). The example applies to open loop applications:

Press

Q2 Quick Set-Up

par. K-01 Language

Set language

par. K-02 Motor Speed Unit

Set motor speed in Hz or RPM

par. P-02 Motor Power [HP] or par. P-07 Motor
Power [kW]

Set Motor nameplate power

par. F-05 Motor Rated Voltage

Set Nameplate voltage

par. F-04 Base Frequency

Set Nameplate frequency

par. P-03 Motor Current

Set Nameplate current

par. P-06 Base Speed

Set Nameplate speed in RPM

par. F-01 Frequency Setting 1

Set reference source

par. F-02 Operation Method

Select which reference site to activate

par. F-07 Accel Time 1

Set the accel time with reference to synchronous motor speed, n

s

par. F-08 Decel Time 1

Set the decel time time with reference to synchronous motor speed,
n

s

par. F-10 Electronic Overload

Set motor thermal protection

par. F-15 Motor Speed High Limit [Hz] or par.
F-17 Motor Speed High Limit [RPM]

Set motor speed high limit in Hz or RPM

par. F-16 Motor Speed Low Limit [Hz] or par.
F-18 Motor Speed Low Limit [RPM]

Set motor speed low limit in Hz or RPM

par. H-08 Reverse Lock

Set allowed rotation direction

par. P-04 Auto Tune

Set desired auto tune function. Enable complete auto tune is rec-
ommended

AF-650 GP High Power Operating Instructions

72

4

Advertising