Mains Supply 3 x 525- 690 VAC
AF-650 GP

50 HP

60 HP

75 HP

100 HP

125 HP

Heavy Duty/Light Duty*

HD

LD

HD

LD

HD

LD

HD

LD

HD

LD

Typical Shaft output at
550 V [kW]

30

37

37

45

45

55

55

75

75

90

Typical Shaft output at
575 V [HP]

40

50

50

60

60

75

75

100

100

125

Typical Shaft output at
690 V [kW]

37

45

45

55

55

75

75

90

90

110

IP21/Nema 1 Drive Type

41

41

41

41

41

IP54/Nema 12 Drive
Type

41

41

41

41

41

IP00 Open Chassis Drive
Type

42

42

42

42

42

Output current

Continuous
(at 550 V) [A]

48

56

56

76

76

90

90

113

113

137

Intermittent (60 sec
overload)
(at 550 V) [A]

77

62

90

84

122

99

135

124

170

151

Continuous
(at 575/ 690 V) [A]

46

54

54

73

73

86

86

108

108

131

Intermittent (60 sec
overload)
(at 575/ 690 V) [A]

74

59

86

80

117

95

129

119

162

144

Continuous KVA
(at 550 V) [KVA]

46

53

53

72

72

86

86

108

108

131

Continuous KVA
(at 575 V) [KVA]

46

54

54

73

73

86

86

108

108

130

Continuous KVA
(at 690 V) [KVA]

55

65

65

87

87

103

103

129

129

157

Max. input current

Continuous
(at 550 V ) [A]

53

60

60

77

77

89

89

110

110

130

Continuous
(at 575 V ) [A]

51

58

58

74

74

85

85

106

106

124

Continuous
(at 690 V ) [A]

50

58

58

77

77

87

87

109

109

128

Max. cable size, mains,
motor, load share and
brake [mm

2

(AWG)]

2x70 (2x2/0)

Max. external pre-fuses
[A]

1

125

160

200

200

250

Estimated power loss
at rated max. load [W]

4)

1355

1458

1459

1717

1721

1913

1913

2262

2264

2662

Weight,
Unit Size IP21, IP 54 [kg]

96

Weight,
Unit Size IP00 [kg]

82

Efficiency

4)

0.97

0.97

0.98

0.98

0.98

Output frequency

0 - 600 Hz

Heatsink overtemp. trip

85 °C

Power card ambient trip

60 °C