Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 111

Advertising
background image

Mains Supply 3 x 380 - 500 VAC
AF-650 GP

600 HP

650 HP

750 HP

900 HP

1000 HP

1200 HP

Heavy Duty/Light Duty*

HD

LD

HD

LD

HD

LD

HD

LD

HD

LD

HD

LD

Typical Shaft output
at 400 V [kW]

450

500

500

560

560

630

630

710

710

800

800

1000

Typical Shaft output
at 460 V [HP]

600

650

650

750

750

900

900

1000

1000

1200

1200

1350

Typical Shaft output
at 500 V [kW]

530

560

560

630

630

710

710

800

800

1000

1000

1100

IP21/Nema 1 and
IP54/Nema 12 Drive
Types without/with
options cabinet

61/ 63

61/ 63

61/ 63

61/ 63

62/ 64

62/ 64

Output current
Continuous
(at 400 V) [A]

800

880

880

990

990

1120

1120

1260

1260

1460

1460

1720

Intermittent (60 sec
overload)
(at 400 V) [A]

1200

968

1320

1089

1485

1232

1680

1386

1890

1606

2190

1892

Continuous
(at 460/ 500 V) [A]

730

780

780

890

890

1050

1050

1160

1160

1380

1380

1530

Intermittent (60 sec
overload)
(at 460/ 500 V) [A]

1095

858

1170

979

1335

1155

1575

1276

1740

1518

2070

1683

Continuous KVA
(at 400 V) [KVA]

554

610

610

686

686

776

776

873

873

1012

1012

1192

Continuous KVA
(at 460 V) [KVA]

582

621

621

709

709

837

837

924

924

1100

1100

1219

Continuous KVA
(at 500 V) [KVA]

632

675

675

771

771

909

909

1005

1005

1195

1195

1325

Max. input current

Continuous
(at 400 V ) [A]

779

857

857

964

964

1090

1090

1227

1227

1422

1422

1675

Continuous (at 460/
500 V) [A]

711

759

759

867

867

1022

1022

1129

1129

1344

1344

1490

Max. cable size,motor
[mm

2

(AWG

2)

)]

8x150

(8x300 mcm)

12x150

(12x300 mcm)

Max. cable size,mains
[mm

2

(AWG

2)

)]

8x240

(8x500 mcm)

Max. cable size, load-
sharing [mm

2

(AWG

2)

)]

4x120

(4x250 mcm)

Max. cable size, brake
[mm

2

(AWG

2)

)

4x185

(4x350 mcm)

6x185

(6x350 mcm)

Max. external pre-
fuses [A]

1

1600

2000

2500

Estimated power loss
at rated max. load
[W]

4)

Weight,
Unit Size IP21, IP 54
[kg]

1004/ 1299

1004/ 1299

1004/ 1299

1004/ 1299

1246/ 1541

1246/ 1541

Weight Rectifier Mod-
ule [kg]

102

102

102

102

136

136

Weight Inverter Mod-
ule [kg]

102

102

102

136

102

102

Efficiency

4)

0.98

Output

frequency

0-600

Hz

Heatsink overtemp.
trip

95 °C

Power card ambient
trip

68 °C

* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s

AF-650 GP High Power Operating Instructions

110

5

Advertising