Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual
Page 107
Control card, RS 485 serial communication:
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS 485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV).
Control card, USB serial communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection earth. Use only an isolated laptop as PC connection to the USB connector on the frequency
converter.
Relay outputs:
Programmable relay outputs
2
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
240 V AC, 2 A
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
60 V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load)
24 V DC, 0.1A
Relay 02 Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
400 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load)
80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load)
24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load)
240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
240 V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load)
50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
over-voltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
150 m
Max. motor cable length, unscreened/unarmoured
300 m
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
1.5 mm
2
/16 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves
1 mm
2
/18 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
/ 24 AWG
Control card performance:
Scan interval
1 ms
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz
+/- 0.003 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19)
≤± 0.1 msec
System response time (terminals 18, 19, 27, 29, 32, 33)
≤ 2 ms
Speed control range (open loop)
1:100 of synchronous speed
Speed control range (closed loop)
1:1000 of synchronous speed
Speed accuracy (open loop)
30 - 4000 rpm: error ±8 rpm
Speed accuracy (closed loop), depending on resolution of feedback device
0 - 6000 rpm: error ±0.15 rpm
All control characteristics are based on a 4-pole asynchronous motor
AF-650 GP High Power Operating Instructions
106
5