Terminal locations - 52
Take the following position of the terminals into consideration when designing the cable access.

Illustration 3.19: IP00 Open Chassis drive type power connection positions

Illustration 3.20: IP00 Open Chassis drive type power connection positions

Note that the power cables are heavy and difficult to bend. Consider the optimum position of the frequency converter for ensuring easy installation of the cables.
Each terminal allows use of up to 4 cables with cable lugs or use of standard box lug. Earth is connected to relevant termination point in the drive.

AF-650 GP High Power Operating Instructions