Par. f-07 accel time 1, Par. f-01 frequency setting 1, Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 75

Advertising
background image

P-03 Motor Current

Range:

Function:

7.20 A*

[0.10 - 10000.00 A]

Enter the nominal motor current value from the motor nameplate data. This data is used for calculating
motor torque, motor thermal protection etc.

NB!
This parameter cannot be adjusted while the motor is running.

P-06 Base Speed

Range:

Function:

1420. RPM* [100 - 60000 RPM]

Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating
automatic motor compensations.

NB!
This parameter cannot be changed while the motor is running.

F-01 Frequency Setting 1

Option:

Function:

Select the reference input to be used for the first reference signal. par. F-01 Frequency Setting 1, par.
C-30 Frequency Command 2 and par. C-34 Frequency Command 3 define up to three different reference
signals. The sum of these reference signals defines the actual reference.

[0]

No function

[1] *

Analog Input 53

[2]

Analog Input 54

[7]

Frequency input 29

[8]

Frequency input 33

[11]

Local bus reference

[20]

Digital Potentiometer

[21]

Analog input X30-11

(OPCGPIO - General Purpose I/O Option Module)

[22]

Analog input X30-12

(OPCGPIO - General Purpose I/O Option Module)

F-02 Operation Method

Option:

Function:

Select which reference site to activate.

[0] *

Linked to Hand / Auto

Use local reference when in Hand mode; or remote reference when in Auto mode.

[1]

Remote

Use remote reference in both Hand mode and Auto mode.

[2]

Local

Use local reference in both Hand mode and Auto mode.

NB!
When set to Local [2], the frequency converter will start with this setting again following a 'power down'.

F-07 Accel Time 1

Range:

Function:

3.00 s*

[0.01 - 3600.00 s]

Enter the accel time, i.e. the acceleration time from 0 RPM to the synchronous motor speed n

S

. Choose a

accel time such that the output current does not exceed the current limit in par. F-43 Current Limit during
ramping. The value 0.00 corresponds to 0.01 sec. in speed mode. See decel time in par. F-08 Decel Time
1
.

AF-650 GP High Power Operating Instructions

74