Pulse/encoder inputs:

Programmable pulse/encoder inputs

2/1

Terminal number pulse/encoder

29, 33

1)

/ 32

2)

, 33

2)

Max. frequency at terminal 29, 32, 33

110 kHz (Push-pull driven)

Max. frequency at terminal 29, 32, 33

5 kHz (open collector)

Min. frequency at terminal 29, 32, 33

4 Hz

Voltage level

see section on Digital input

Maximum voltage on input

28 V DC

Input resistance, R

i

approx. 4 kΩ

Pulse input accuracy (0.1 - 1 kHz)

Max. error: 0.1% of full scale

Encoder input accuracy (1 - 110 kHz)

Max. error: 0.05 % of full scale

The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Pulse inputs are 29 and 33
2) Encoder inputs: 32 = A, and 33 = B

Digital output:

Programmable digital/pulse outputs

2

Terminal number

27, 29

1)

Voltage level at digital/frequency output

0 - 24 V

Max. output current (sink or source)

40 mA

Max. load at frequency output

1 kΩ

Max. capacitive load at frequency output

10 nF

Minimum output frequency at frequency output

0 Hz

Maximum output frequency at frequency output

32 kHz

Accuracy of frequency output

Max. error: 0.1 % of full scale

Resolution of frequency outputs

12 bit

1) Terminal 27 and 29 can also be programmed as input.

The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Analog output:

Number of programmable analog outputs

1

Terminal number

42

Current range at analog output

0/4 - 20 mA

Max. load GND - analog output

500 Ω

Accuracy on analog output

Max. error: 0.5 % of full scale

Resolution on analog output

12 bit

The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control card, 24 V DC output:

Terminal number

12, 13

Output voltage

24 V +1, -3 V

Max. load

200 mA

The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs.

Control card, 10 V DC output:

Terminal number

50

Output voltage

10.5 V ±0.5 V

Max. load

15 mA

The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.