Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 105

Advertising
background image

Safe stop Terminal 37

3)

(Terminal 37 is fixed PNP logic):

Voltage level

0 - 24 V DC

Voltage level, logic'0' PNP

< 4 V DC

Voltage level, logic'1' PNP

>20 V DC

Nominal input current at 24 V

50 mA rms

Nominal input current at 20 V

60 mA rms

Input capacitance

400 nF

All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.

2) Except safe stop input Terminal 37.
3) Terminal 37 can only be used as safe stop input. Terminal 37 is suitable for category 3 installations according to EN 954-1 (safe stop according to category 0 EN
60204-1) as required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in conformance with EN 60204-1, EN 50178,
EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the related information and instructions in the AF-650 GP Design
Guide.

Analog inputs:

Number of analog inputs

2

Terminal number

53, 54

Modes

Voltage or current

Mode select

Switch S201 and switch S202

Voltage mode

Switch S201/switch S202 = OFF (U)

Voltage level

-10 to +10 V (scaleable)

Input resistance, R

i

approx. 10 kΩ

Max. voltage

± 20 V

Current mode

Switch S201/switch S202 = ON (I)

Current level

0/4 to 20 mA (scaleable)

Input resistance, R

i

approx. 200 Ω

Max. current

30 mA

Resolution for analog inputs

10 bit (+ sign)

Accuracy of analog inputs

Max. error 0.5% of full scale

Bandwidth

100 Hz

The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

AF-650 GP High Power Operating Instructions

104