Unit Size

Terminal

Torque

Bolt size

41, 42, 43 and 44

Mains
Motor

19 Nm (168 in-lbs)

M10

Load sharing
Brake

9.5 (84 in-lbs)

M8

51 and 52

Mains
Motor
Load sharing

19 NM (168 in-lbs)

M10

Brake

9.5 (84 in-lbs)

M8

61, 62, 63 and 64

Mains
Motor

19 Nm (168 in-lbs)

M10

Load sharing
Brake
Regen

19 Nm (168 in-lbs)
9.5 Nm (84 in-lbs)
19 Nm (168 in-lbs)

M10
M8
M10

Table 3.3: Torque for terminals

3.6.6 Shielded Cables

It is important that shielded and armoured cables are connected in a proper way to ensure high EMC immunity and low emissions.

Connection can be made using either cable glands or clamps:

EMC cable glands: Generally available cable glands can be used to ensure an optimum EMC connection.

EMC cable clamp: Clamps allowing easy connection are supplied with the frequency converter.

3.6.7 Motor cable

The motor must be connected to terminals U/T1/96, V/T2/97, W/T3/98. Earth to terminal 99. All types of three-phase asynchronous standard motors can be used
with a frequency converter unit. The factory setting is for clockwise rotation with the frequency converter output connected as follows:

Terminal No.

Function

96, 97, 98, 99

Mains U/T1, V/T2, W/T3
Earth

• Terminal U/T1/96 connected to U-phase

• Terminal V/T2/97 connected to V-phase

• Terminal W/T3/98 connected to W-phase

The direction of rotation can be changed by switching two phases in the motor cable or by changing the setting of par. H-08 Reverse Lock.
Motor rotation check can be performed using par. P-08 Motor Rotation Check and following the steps shown in the display.

AF-650 GP High Power Operating Instructions

55

3