background image

Mains Supply 3 x 525- 690 VAC
AF-650 GP

550 HP

650 HP

750 HP

Heavy Duty/Light Duty*

HD

LD

HD

LD

HD

LD

Typical Shaft output at 550 V [kW]

315

400

400

450

450

500

Typical Shaft output at 575 V [HP]

400

500

500

600

600

650

Typical Shaft output at 690 V [kW]

400

500

500

560

560

630

IP21/Nema 1 Drive Type

51

51

51

IP54/Nema Drive Type

51

51

51

IP00 Open Chassis Drive Type

52

52

52

Output current
Continuous
(at 550 V) [A]

429

523

523

596

596

630

Intermittent (60 sec overload)
(at 550 V) [A]

644

575

785

656

894

693

Continuous
(at 575/ 690 V) [A]

410

500

500

570

570

630

Intermittent (60 sec overload)
(at 575/ 690 V) [A]

615

550

750

627

855

693

Continuous KVA
(at 550 V) [KVA]

409

498

498

568

568

600

Continuous KVA
(at 575 V) [KVA]

408

498

498

568

568

627

Continuous KVA
(at 690 V) [KVA]

490

598

598

681

681

753

Max. input current

Continuous
(at 550 V ) [A]

413

504

504

574

574

607

Continuous
(at 575 V) [A]

395

482

482

549

549

607

Continuous
(at 690 V) [A]

395

482

482

549

549

607

Max. cable size, mains, motor and
load share [mm

2

(AWG)]

4x240 (4x500 mcm)

4x240 (4x500 mcm)

4x240 (4x500 mcm)

Max. cable size, brake [mm

2

(AWG)]

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

Max. external pre-fuses [A]

1

700

900

900

Estimated power loss
at rated max. load [W]

4)

5818

7249

7671

8727

8715

9673

Weight,
Unit Size IP21, IP 54 [kg]

263

272

313

Weight,
Unit Size IP00 [kg]

221

236

277

Efficiency

4)

0.98

Output

frequency

0 - 500 Hz

Heatsink overtemp. trip

85 °C

Power card ambient trip

68 °C

* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s