Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 120

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter

Reference

54

Auto Tune motor too small

X

55

Auto Tune parameter out of range

X

56

Auto Tune interrupted by user

X

57

Auto Tune time-out

X

58

Auto Tune internal fault

X

X

59

Current limit

X

61

Tracking Error

(X)

(X)

par. H-20 Motor Feedback

Loss Function

62

Output Frequency at Maximum Limit

X

63

Mechanical Brake Low

(X)

par. B-20 Release Brake

Current

64

Voltage Limit

X

65

Control Board Over-temperature

X

X

X

66

Heat sink Temperature Low

X

67

Option Module Configuration has Changed

X

68

Safe Stop

(X)

(X)

1)

par. E-07 Terminal 37 Safe

Stop

69

Pwr. Card Temp

X

X

70

Illegal Drive configuration

X

71

Safe Stop

X

X

1)

par. E-07 Terminal 37 Safe

Stop

72

Dangerous Failure

X

1)

par. E-07 Terminal 37 Safe

Stop

73

Safe Stop Auto Restart

77

Reduced power mode

X

par. SP-59 Actual Number

of Inverter Units

79

Illegal PS config

X

X

80

Drive Restored to Factory Settings

X

81

CSIV corrupt

82

CSIV parameter error

85

Profibus/Profisafe Error

90

Encoder Loss

(X)

(X)

par. EC-61 Feedback Sig-

nal Monitoring

91

Analog input 54 wrong settings

X

S202

243

Brake IGBT

X

X

244

Heatsink temp

X

X

X

245

Heatsink sensor

X

X

246

Pwr.card supply

X

X

247

Pwr.card temp

X

X

248

Illegal PS config

X

X

250

New spare part

X

251

New Model Number

X

X

Table 6.2: Alarm/Warning code list

(X) Dependent on parameter
1) Can not be Auto reset via par. H-04 Auto-Reset (Times)
A trip is the action when an alarm has appeared. The trip will coast the motor and can be reset by pressing the reset button or make a reset by a digital input (Par.
E-1# [1]). The origin event that caused an alarm cannot damage the frequency converter or cause dangerous conditions. A trip lock is an action when an alarm
occurs, which may cause damage to frequency converter or connected parts. A Trip Lock situation can only be reset by a power cycling.

LED indication

Warning

yellow

Alarm

flashing red

Trip locked

yellow and red

AF-650 GP High Power Operating Instructions

119

6

Advertising