ALARM 53, Auto tune motor too big:
The motor is too big for the Auto tune to be carried out.

ALARM 54, Auto tune motor too small:
The motor is too big for the Auto tune to be carried out.

ALARM 55, Auto tune par. out of range:
The par. values found from the motor are outside acceptable range.

ALARM 56, Auto tune interrupted by user:
The Auto tune has been interrupted by the user.

ALARM 57, Auto tune time-out:
Try to start the Auto tune again a number of times, until the Auto tune is carried
out. Please note that repeated runs may heat the motor to a level where the
resistance Rs and Rr are increased. In most cases, however, this is not critical.

ALARM 58, Auto tune internal fault:
Contact your GE supplier.

WARNING 59, Current limit:
Contact your GE supplier.

WARNING 61, Encoder loss:
Contact your GE supplier.

WARNING 62, Output Frequency at Maximum Limit:
The output frequency is higher than the value set in par. F-03 Max Output
Frequency 1

ALARM 63, Mechanical Brake Low:
The actual motor current has not exceeded the “release brake” current within
the “Start delay” time window.

WARNING 64, Voltage Limit:
The load and speed combination demands a motor voltage higher than the
actual DC link voltage.

WARNING/ALARM/TRIP 65, Control Card Over Temperature:
Control card over temperature: The cutout temperature of the control card is
80° C.

WARNING 66, Heatsink Temperature Low:
The heatsink temperature is measured as 0° C. This could indicate that the
temperature sensor is defect and thus the fan speed is increased to the max-
imum in case the power part or control card is very hot.

ALARM 67, Option Configuration has Changed:
One or more options have either been added or removed since the last power-
down.

ALARM 68, Safe Stop Activated:
Safe Stop has been activated. To resume normal operation, apply 24 V DC to
terminal 37, then send a reset signal (via Bus, Digital I/O, or by pressing [RE-
SET]). For correct and safe use of the Safe Stop function follow the related
information and instructions in the AF-650 GP Design Guide

ALARM 69, Pwr.card temp:
Power card over temperature.

ALARM 70, Illegal Drive Configuration:
Actual combination of control board and power board is illegal.

Warning 73, Safe Stop Auto Restart:
Safe Stopped, the drive may autostart when Safe Stop is removed

WARNING 77, Reduced power mode:
This warning indicates that the drive is operating in reduced power mode (i.e.
less than the allowed number of inverter sections). This warning will be gen-
erated on power cycle when the drive is set to run with fewer inverters and
will remain on.

ALARM 79, Illegal PS config:
Current sensor connector at power card not installed or the scaling card is
the incorrect part number or is not installed

ALARM 80, Drive Restored to Factory Settings:
Parameter settings are restored to factory settings after a manual (three-
finger) reset.

WARNING 81, CSIV corrupt:
CSIV file has syntax errors.

WARNING 82, CSIV parameter error:
CSIV parameter error

WARNING 85, Dang fail PB:
Profibus/Profisafe Error

ALARM 91, Analog Input 54 Wrong Settings:
Switch S202 has to be set in position OFF (voltage input) when a KTY sensor
is connected to analog input terminal 54.

ALARM 243, Brake IGBT:
Unit size 6 equivalent to fault 27 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 244, Heatsink temp:
Unit size 6 equivalent to fault 29 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 245, Heatsink sensor:
Unit size 6 equivalent to fault 39 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 246, Pwr. card supply:
Unit size 6 equivalent to fault 46 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 247, Pwr. card temp:
Unit size 6 equivalent to fault 69 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 248, Illegal PS config:
Unit size 6 equivalent to fault 79 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 250, New Spare Part:
The power or Switch Mode Power Supply has been exchanged. The frequency
converter type code must be restored in the EEPROM. Remember to select
‘Save to EEPROM’ to complete.

ALARM 251, New Model Number:
The Frequency Converter has got a new Model Number.