Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 116

Advertising
background image

Mains Supply 3 x 525- 690 VAC
AF-650 GP

900 HP

1000 HP

1200 HP

1250 HP

1350 HP

Heavy Duty/Light Duty*

HD

LD

HD

LD

HD

LD

HD

LD

HD

LD

Typical Shaft output at
550 V [kW]

500

560

560

670

670

750

750

850

850

1000

Typical Shaft output at
575 V [HP]

650

750

750

950

950

1050

1050

1150

1150

1350

Typical Shaft output at
690 V [kW]

630

710

710

800

800

900

900

1000

1000

1200

IP21/Nema 1 and IP54/
Nema 12 Drive Types
without/with options
cabinet

61/ 63

61/ 63

61/ 63

62/ 64

62/ 64

Output current
Continuous
(at 550 V) [A]

659

763

763

889

889

988

988

1108

1108

1317

Intermittent (60 sec
overload)
(at 550 V) [A]

989

839

1145

978

1334

1087

1482

1219

1662

1449

Continuous
(at 575/ 690 V) [A]

630

730

730

850

850

945

945

1060

1060

1260

Intermittent (60 sec
overload)
(at 575/ 690 V) [A]

945

803

1095

935

1275

1040

1418

1166

1590

1386

Continuous KVA
(at 550 V) [KVA]

628

727

727

847

847

941

941

1056

1056

1255

Continuous KVA
(at 575 V) [KVA]

627

727

727

847

847

941

941

1056

1056

1255

Continuous KVA
(at 690 V) [KVA]

753

872

872

1016

1016

1129

1129

1267

1267

1506

Max. input current

Continuous
(at 550 V ) [A]

642

743

743

866

866

962

962

1079

1079

1282

Continuous
(at 575 V) [A]

613

711

711

828

828

920

920

1032

1032

1227

Continuous
(at 690 V) [A]

613

711

711

828

828

920

920

1032

1032

1227

Max. cable size, motor
[mm

2

(AWG

2)

)]

8x150

(8x300 mcm)

12x150

(12x300 mcm)

Max. cable size,mains
[mm

2

(AWG

2)

)]

8x240

(8x500 mcm)

Max. cable size, load-
sharing [mm

2

(AWG

2)

)]

4x120

(4x250 mcm)

Max. cable size, brake
[mm

2

(AWG

2)

)

4x185

(4x350 mcm)

6x185

(6x350 mcm)

Max. external pre-fuses
[A]

1

1600

2000

Estimated power loss
at rated max. load [W]

4)

Weight,
Unit Size IP21, IP 54 [kg]

1004/ 1299

1004/ 1299

1004/ 1299

1246/ 1541

1246/ 1541

Weight, Rectifier Module
[kg]

102

102

102

136

136

Weight, Inverter Module
[kg]

102

102

136

102

102

Efficiency

4)

0.98

Output frequency

0-500 Hz

Heatsink overtemp. trip

85 °C

Power card ambient trip

68 °C

* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s

1) For type of fuse see section Fuses.

2) American Wire Gauge.

3) Measured using 5 m screened motor cables at rated load and rated frequency.

4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the frequency converter
and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
Keypad and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses. (Though typical
only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).

AF-650 GP High Power Operating Instructions

115

5

Advertising