Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 109

Advertising
background image

Mains Supply 3 x 380 - 500 VAC
AF-650 GP

125 HP

150 HP

200 HP

250 HP

300 HP

Heavy Duty/Light Duty*

HD

LD

HD

LD

HD

LD

HD

LD

HD

LD

Typical Shaft output at
400 V [kW]

90

110

110

132

132

160

160

200

200

250

Typical Shaft output at
460 V [HP]

125

150

150

200

200

250

250

300

300

350

Typical Shaft output at
500 V [kW]

110

132

132

160

160

200

200

250

250

315

IP21/Nema 1 Drive Type

41

41

42

42

42

IP54/Nema 12 Drive
Type

41

41

42

42

42

IP00 Open Chassis Drive
Type

43

43

44

44

44

Output current
Continuous
(at 400 V) [A]

177

212

212

260

260

315

315

395

395

480

Intermittent (60 sec
overload)
(at 400 V) [A]

266

233

318

286

390

347

473

435

593

528

Continuous
(at 460/ 500 V) [A]

160

190

190

240

240

302

302

361

361

443

Intermittent (60 sec
overload)
(at 460/ 500 V) [A]

240

209

285

264

360

332

453

397

542

487

Continuous KVA
(at 400 V) [KVA]

123

147

147

180

180

218

218

274

274

333

Continuous KVA
(at 460 V) [KVA]

127

151

151

191

191

241

241

288

288

353

Continuous KVA
(at 500 V) [KVA]

139

165

165

208

208

262

262

313

313

384

Max. input current

Continuous
(at 400 V ) [A]

171

204

204

251

251

304

304

381

381

463

Continuous
(at 460/ 500 V) [A]

154

183

183

231

231

291

291

348

348

427

Max. cable size, mains
motor, brake and load
share [mm

2

(AWG

2)

)]

2 x 70

(2 x 2/0)

2 x 70

(2 x 2/0)

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

Max. external pre-fuses
[A]

1

300

350

400

500

600

Estimated power loss
at rated max. load [W]

4)

2641

3234

2995

3782

3425

4213

3910

5119

4625

5893

Weight,
Unit Size IP21, IP 54 [kg]

96

104

125

136

151

Weight,
Unit Size IP00 [kg]

82

91

112

123

138

Efficiency

4)

0.98

Output frequency

0 - 800 Hz

Heatsink overtemp. trip

85 °C

90 °C

105 °C

105 °C

115 °C

Power card ambient trip

60 °C

* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s

AF-650 GP High Power Operating Instructions

108

5