6 electrical installation – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 44

Advertising
background image

3.6 Electrical Installation

3.6.1 Power Connections

Cabling and Fusing

NB!
Cables General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper (75°C) conductors are recommended.

The power cable connections are situated as shown below. Dimensioning of cable cross section must be done in accordance with the current ratings and local
legislation. See the Specifications section for details.

For protection please see fuse in the tables of the fuse section. Always ensure that proper fusing is made according to local regulation.

NB!
Use a screened/armoured motor cable to comply with EMC emission specifications. For more information, see EMC specifications in the AF-650 GPDesign
Guide
.

See section General Specifications for correct dimensioning of motor cable cross-section and length.

AF-650 GP High Power Operating Instructions

43

3

Advertising