Af-650 gp high power operating instructions – GE Industrial Solutions AF-650 GP General Purpose Drive (460_575_690V 125HP and above) User Manual

Page 119

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter

Reference

1

10 Volts low

X

2

Live zero error

(X)

(X)

par. AN-01 Live Zero Time-

out Function

3

No motor

(X)

par. H-80 Function at Stop

4

Mains phase loss

(X)

(X)

(X)

par. SP-12 Function at Line

Imbalance

5

DC link voltage high

X

6

DC link voltage low

X

7

DC over-voltage

X

X

8

DC under voltage

X

X

9

Inverter overloaded

X

X

10

Motor Electronic OL over temperature

(X)

(X)

par. F-10 Electronic Over-

load

11

Motor thermistor over temperature

(X)

(X)

par. F-10 Electronic Over-

load

12

Torque limit

X

X

13

Over Current

X

X

X

14

Earth Fault

X

X

X

15

Hardware mismatch

X

X

16

Short Circuit

X

X

17

Control word time-out

(X)

(X)

par. O-04 Control Word

Timeout Function

22

Hoist Mech. Brake

23

Internal Fan Fault

X

24

External Fan Fault

X

par. SP-53 Fan Monitor

25

Brake resistor short-circuited

X

26

Brake resistor power limit

(X)

(X)

par. B-13 Braking Thermal

Overload

27

Brake chopper short-circuited

X

X

28

Brake check

(X)

(X)

par. B-15 Brake Check

29

Heatsink temp

X

X

X

30

Motor phase U missing

(X)

(X)

(X)

par. H-78 Missing Motor

Phase Function

31

Motor phase V missing

(X)

(X)

(X)

par. H-78 Missing Motor

Phase Function

32

Motor phase W missing

(X)

(X)

(X)

par. H-78 Missing Motor

Phase Function

33

Inrush Fault

X

X

34

Network communication fault

X

X

36

Mains failure

X

X

38

Internal Fault

X

X

39

Heatsink sensor

X

X

40

Overload of Digital Output Terminal 27

(X)

par. E-00 Digital I/O Mode,

par. E-51 Terminal 27 Mode

41

Overload of Digital Output Terminal 29

(X)

par. E-00 Digital I/O Mode,

par. E-52 Terminal 29 Mode

42

Overload of Digital Output On X30/6

(X)

par. E-56 Term X30/6 Digi

Out (OPCGPIO)

42

Overload of Digital Output On X30/7

(X)

par. E-57 Term X30/7 Digi

Out (OPCGPIO)

46

Pwr. card supply

X

X

47

24 V supply low

X

X

X

48

1.8 V supply low

X

X

49

Speed limit

X

50

Auto Tune calibration failed

X

51

Auto Tune check U

nom

and I

nom

X

52

Auto Tune low I

nom

X

53

Auto Tune motor too big

X

Table 6.1: Alarm/Warning code list

AF-650 GP High Power Operating Instructions

118

6

Advertising