Surroundings:

Enclosure

IP00 Open Chassis, IP21/Nema 1, and IP54/Nema 12

Vibration test

0.7 g

Max. relative humidity

5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation

Aggressive environment (IEC 60068-2-43

class H

2

5

Ambient temperature

Max. 45 °C

1) For higher ambient temperature, see special conditions in the AF-650 GP Design Guide

Minimum ambient temperature during full-scale operation

0 °C

Minimum ambient temperature at reduced performance

- 10 °C

Temperature during storage/transport

-25 - +65/70 °C

Maximum altitude above sea level without derating

1000 m

Derating for high altitude, see special conditions in the AF-650 GP Design Guide

EMC standards, Emission

EN 61800-3, EN 61000-6-3/4, EN 55011

EMC standards, Immunity

EN 61800-3, EN 61000-6-1/2,

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6

See section on special conditions in the AF-650 GP Design Guide Please see www.geelectrical.com/drives for more information.

Protection and Features:

Electronic thermal motor protection against overload.

Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches a predefined level. An overload temper-
ature cannot be reset until the temperature of the heatsink is below the values stated in the tables on the following pages (Guideline - these temperatures
may vary for different power sizes, Unit Sizes, enclosure ratings etc.).

The frequency converter is protected against short-circuits on motor terminals U, V, W.

If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).

Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.

The frequency converter constantly checks for critical levels of internal temperature, load current, high voltage on the intermediate circuit and low motor
speeds. As a response to a critical level, the frequency converter can adjust the switching frequency and/ or change the switching pattern in order to
ensure the performance of the drive.

AF-650 GP High Power Operating Instructions

107

5

Advertising